Inliner Solutions, LLC – ITB: M/W/SBE Certified Firms
Project: ARPA Sewer Improvements
Project Location: Adairsville, GA
Bid Due Date: 07/06/2023
Quotes Returned: 07/03/2023
Scopes:
- Pre & Post Pipe Burst CCTV & Cleaning (562998)
- Open Cut Utility Repairs (238910)
- Sewer Removal & Replacement
- Manhole removal & Replacement
- Manhole F&C Replacement
- Asphalt & Concrete Restorations (237310)
- Sanitary Sewer Lift Station Upgrades (237110)
- Manhole Rehabilitation (237110)
- The 100 percent solids, solvent-free ultra high-build epoxy system shall exhibit the following characteristics:
- a. Application Temperature – 50 degrees F, minimum
- b. Thickness – 125 mils minimum
- c. Color – White, Light Blue, or Beige
- d. Compressive Strength (per ASTM D695) – 8,800 psi minimum
- e. Tensile Strength (per ASTM D638) – 7,500 psi minimum
- f. Hardness, Shore D (per ASTM D4541) – 70 minimum
- g. Abrasion Resistance (per ASTM D4060 CS 17F Wheel) – 80 mg loss maximum
- h. Flexural Modulus (per ASTM D790) – 400,000 psi minimum
- i. Flexural Strength (per ASTM D790) – 12,000 psi minimum
- j. Adhesion to Concrete, mode of failure (ASTM D4541): Substrate (concrete) failure
- k. Chemical Resistance (ASTM D543/G20) all types of service for:
- 1) Municipal sanitary sewer environment
- 2) Sulfuric acid, 30 percent
- 3) Sodium hydroxide, 5 percent
- The 100 percent solids, solvent-free ultra high-build epoxy system shall exhibit the following characteristics:
- Material Suppliers (326199)
- PVC Pipe & Fittings
- HDPE Pipe & fittings
- Sewer Saddle for lateral reconnects
- Manhole Precast structures
- Manhole Ring & Covers
- Traffic Control (561990)
- Single Lane Closure with Flaggers , 12 HR Shift
Specs/Plans /Questions– Ashden Middlebrooks | ashden.middlebrooks@puriscorp.com | 470-503-5624